However, using an Allen-Bradley motor with your drive removes the . Н Installation guidelines called out in Appendix D of the User’s Manual. Installation Instructions IN. May, Allen-Bradley. Dynamic Brake. Cat. No. KAA KBA03, KBA06, KBA Table of Contents. Find great deals for Allen Bradley Adjustable Frequency AC Drive User Manual. Shop with confidence on eBay!.

Author: Mizilkree Doujind
Country: Guatemala
Language: English (Spanish)
Genre: Health and Food
Published (Last): 26 April 2017
Pages: 234
PDF File Size: 3.56 Mb
ePub File Size: 10.32 Mb
ISBN: 599-5-45777-761-4
Downloads: 23764
Price: Free* [*Free Regsitration Required]
Uploader: JoJodal

Inspect to ensure that the ambient temperature limit has not been exceeded. Error 2 – The number of parameters in saved profile does not equal master number. Hz Sel Fault – F30 An unconnected adapter has been selected as the active frequency source.

DC Bus voltage fell below the minimum value. Motor Stall Fault – F6 The motor has stalled If the motor is drawing excessive current, the motor load is excessive and will not allow the drive to accelerate to set speed. The Adjustable Frequency AC Drive is a variable speed drive designed to control the speed of three-phase AC induction motors in a variety of demanding applications where flexibility, performance and ease of use are essential.

Related Posts (10)  DRAUPADI THE FIRE-BORN PRINCESS PDF

Skip frequencies and skip bandwith eliminate all operating frequencies. The Adjustable Frequency AC drive is available with ratings 0. Reprogram Fault – F48 May occur when drive parametersare reset to default settings. Reduce [Start Boost] if applicable.

D Micro Programmable Logic Controllers. Overcurrent Fault – F12 Overcurrent is detected in overcurrent hardware trip circuit. Fast repairs at low costs. Error 4 – Saved data for parameter not correct for new drive. Check the AC line for high line voltage or transient conditions. Serial Fault – F10 An active local bus adapter is disconnected while it possesses control of a local bus function. If not, manually program any remaining parameters. No valid operating frequency. Stop drive, then re-run download.

Correct the cause of the fault and manually clear by cycling the stop command or cycling power. Phase V Fault – F39 A phase to ground fault has been detected between the drive and motor in this phase. Drive Reset Fault – F22 May occur on power-up. Connect proper adapter or change active frequency source. Verify that all parameters have been programmed. Check motor for grounded phase. Change [Cable Length] to “Long” if applicable.

1305 AC Drives

An active local bus adapter maunal disconnected while it possesses control of a local bus function. Check for external noise sources. Overtemperature Fault – F8 Temperature sensor detects excessive heat.

Related Posts (10)  FIQH OF MUSLIM MINORITIES QARADAWI PDF

Check gfd of [Curr Lim Trip En] parameter. Bus overvoltage can also be caused by motor reeneration. Open Pot Fault – F9 An external pot is connected and the ground lead of the pot is disconnected, creating a potential drive overspeed hazard.

Check for a short circuit at the drive output or excessive load conditions at the motor.

Allen Bradley Adjustable Frequency AC Drive AB

Overload Fault – F7 Internal electronic overload trip. Verify that the parameter has been programmed correctly. Check for proper mounting and spacing.

If the motor is drawing excessive current, the motor load is excessive and will not allow the drive to accelerate to set speed. Hz Err Fault – F29 No valid operating frequency. Error 5 – Drive is running while attempting download Repeat operation.

Check for broken wires, loose connections, or transducer loss at mA input, TB2.